NewsPositive Technologies helps patch critical vulnerabilities in an industrial switch
News

Positive Technologies helps patch critical vulnerabilities in an industrial switch

A successful cyberattack could disrupt OT/ICS communications and halt industrial processes.

Experts from PT SWARM have identified five vulnerabilities in the IGS-5225-8P2T4S industrial managed switch. The device is manufactured by PLANET Technology, a Taiwan-based provider of enterprise and industrial networking solutions with a global presence in over 160 countries. By exploiting these security flaws, a threat actor could gain full administrative access to the switch OS or cause a denial-of-service (DoS) condition. When this equipment is deployed within an industrial control system (ICS)1, such an attack could disrupt internal OT/ICS data exchange and potentially shut down critical industrial processes. Following responsible disclosure guidelines, Positive Technologies reported these findings to the manufacturer. PLANET Technology has since released updated firmware versions to address the security issues.

The IGS-5225-8P2T4S industrial managed switch is designed to build L2+ Ethernet networks. It is deployed in industrial control systems as well as other enterprise environments, such as video surveillance networks, where it connects and powers IP cameras via PoE (Power over Ethernet). Built with a rugged metal housing, the device can be installed in industrial cabinets, including outdoor setups, and operates reliably in extreme temperatures ranging from −40 to +75 degrees Celsius.

1 Industrial control system (ICS): an integrated hardware and software system that operates, automates, and monitors industrial facilities.

The switch supports communication with SCADA2 systems using the Modbus TCP protocol. In OT/ICS networks, it routes data between programmable logic controllers (PLCs)3, SCADA platforms, and other critical components. The stable operation of this switch is vital, as it ensures that real-time data about industrial processes and equipment status reaches operator workstations4 and that control commands are transmitted without delay.

The vulnerabilities affect hardware version 1 of the switch running firmware earlier than v1.2412b260707 (as well as specifically version v1.440b210519), and hardware version 2 running firmware earlier than v2.2412b260519. The security flaws, tracked as PT-2026-95413–PT-2026-95457 (CVE-2026-81942–CVE-2026-81946; BDU: 2026-06772–BDU: 2026-06776), have been assigned CVSS 4.0 scores ranging from 6.7 to 8.7. These vulnerabilities were discovered by Positive Technologies researchers Ilya Bubliy, Maksim Gruzin5, Arseny Grigorev, Aleksey Karimov, Ivan Kurnakov, Vladimir Nazarov, Iliya Rogachev, and Ivan Tarakanov.

Before they were patched, all five vulnerabilities could be exploited independently and were not part of a single exploit chain. Three of these security flaws PT-2026-95413 (CVE-2026-81942; BDU: 2026-06772), PT-2026-95415 (CVE-2026-81944; BDU: 2026-06774), and PT-2026-95416 (CVE-2026-81945; BDU: 2026-06775) were found in the web service of the switch. The first vulnerability allowed an attacker to gain full administrative access to the switch OS. The other two were stack-based buffer overflows that could lead to a denial-of-service (DoS) condition, disrupting the normal operation of the switch.

To exploit these flaws, an attacker would need network access to the device's web service via HTTP or HTTPS, as well as valid switch credentials obtained through prior compromise. Exploiting PT-2026-95413 and PT-2026-95415 required only an unprivileged user account, while PT-2026-95416 required administrator privileges.

2 Supervisory control and data acquisition (SCADA): a software platform used to gather, analyze, and visualize data from industrial equipment, and to provide supervisory control over industrial processes.

3 Programmable logic controller (PLC): a specialized hardware device within an ICS used to automate and control industrial machinery.

4 Operator workstations used to monitor and control industrial processes.

5 Employed by Positive Technologies at the time the vulnerabilities were discovered.

The remaining two vulnerabilities affected the mechanisms used to manage and store user credentials. PT-2026-95414 (CVE-2026-81943; BDU: 2026-06773) was caused by an undocumented debug mode command in the switch's command-line interface (CLI)6. Successfully exploiting this flaw would grant full administrative access to the switch OS. To execute this attack, a threat actor would need an administrator account and network access to the CLI via specific network protocols.

Finally, PT-2026-95457 (CVE-2026-81946; BDU: 2026-06776) stemmed from the use of a weak hashing algorithm for password protection. If an attacker managed to obtain a password hash, such as from a backup file, they could easily crack the password and gain unauthorized access to the device.

6 Command-line interface (CLI): an interface used to configure and control the device by entering text-based commands.

"If a vulnerable switch is deployed in an industrial network, taking control of it or knocking it offline could disrupt communication between PLCs, SCADA systems, and other ICS components. Consequently, operators could lose access to real-time equipment data and remote control capabilities. Depending on the facility's automation logic and operational procedures, such an attack could halt industrial processes, leading to significant financial and reputational damage."

Ivan Kurnakov
Ivan KurnakovHead of ICS Security Practice at Positive Technologies

Hardware version 1 of the IGS-5225-8P2T4S switch has reached end-of-life (EOL)7 and typically no longer receives security updates. However, given the high risk of cyberattacks, the vendor followed the recommendations of Positive Technologies researchers and released a special firmware patch (v1.2412b260707) for this version. Users of hardware version 2 must update to firmware v2.2412b260519 or later. If installing the update is not immediately possible, Positive Technologies experts advise restricting access to the switch's web service and CLI from external and corporate networks, and completely disabling the Telnet protocol.

Attempts to exploit these vulnerabilities can be detected using PT Industrial Security Incident Manager (PT ISIM), a solution designed to ensure the cyber resilience of industrial infrastructures. Additionally, advanced network traffic analysis (NTA) and network detection and response (NDR) solutions like PT Network Attack Discovery (PT NAD) can effectively identify this malicious activity, while next-generation firewalls (NGFW) such as PT NGFW can actively block it.

For up-to-date security information, visit the dbugs portal, which aggregates vulnerability data and vendor recommendations for software and hardware from vendors around the world.

7 EOL (End of Life): The end of a device version's life cycle, after which the manufacturer no longer provides regular support, security updates, or further development.